Cài đặt các thông số cơ bản về biến tần S.A.J

Một số mã lỗi biến tần SAJ – Fault Codes

Menu

Fault
code
Fault description Possible causes Remedy
Err02 Over-current during
acceleration
Too fast acceleration Increase acceleration time
Too low input voltage Check the input power
supply or wiring
Lower-rating controller Replace with higher-rating
controller
Err03 Over-current during
deceleration
Too-fast deceleration Increase deceleration time
Too-heavy and large-inertia load Add proper braking units
Err04 Over-current at
constant running
speed
Sudden change of load Check the load
Too low input voltage Check the input power
supply or wiring
Fault
code
Fault description Possible causes Remedy
Lower-rating controller Replace with higher-rating
controller
Err05 Over-voltage during
acceleration
Abnormal input voltage Check input power
Restart the motor when
instantaneous trip-off occurs
Avoid prompt restart when
trip-off
Err06 Over-voltage during
deceleration
Too-fast deceleration Add proper braking units
Abnormal input voltage Check input power supply or
wiring
Err07 Over-voltage at
constant running
speed
Abnormal input voltage Adjust input voltage to
normal range
Err08 Overload of buffer
resistor
Abnormal input voltage A nodrjmusatlirnapnugtevoltage to
Err09 Under voltage of
DC bus
Too-low input voltage C whireicnkg input power supply or
Err10 Controller overload Too fast acceleration Increase acceleration time
Restart the motor when
instantaneous trip-off occurs
Avoid prompt restart when
trip-off
Too-low input voltage Check input power supply or
wiring
Too-heavy load Replace with higher-rating
controller
Err11 Motor overload Incorrect setting of
FA.01&FA.02
Set the parameters correctly
Load too heavy or motor stuck Reduce loador check the
motor
Err12 Input phase loss Abnormal input power source Check input power source
and wiring
Fault
code
Fault description Possible causes Remedy
Power board or control board
failure
Look for technical support
Err13 Output phase loss Broken wires in the output cable Check the wiring and
installation
Broken wires in the motor
winding
Loose output terminals
Err14 Controller overheat Instantaneous over-current of
controller
Refer to over-current
remedy
Output short circuit Re-wiring of output
Too-high ambient temperature Decrease the ambient
temperature if possible
Loose cables or terminals Inspect and tighten the wire
and terminals
Abnormal power circuit Ask for support
Abnormal control PCB board
Err15 External fault External fault signal through DI
terminals
Check external faults
Err16 Communication
fault
Improper baud rate setting Set proper baud rate
Abnormal working of upper
machine
Check upper machine
Long-time communication
interruption
Check communication
devices and cables
Err17 Relay failure Relay cannot pick up Change relay or look for
technical support
Err18 Current detection
fault
Amplifying circuit abnormal Ask for technical support
Hall sensor is damaged
Fault
code
Fault description Possible causes Remedy
Power circuit abnormal
Err19 Motor tuning
failure
Incorrect settings of motor
parameters
Set motor parameters
according to motor plate
Err21 Parameters writing
& reading failure
Control board failure. C lohoaknfgoeratencohthneicrablosaurpdpoorrt
Err22 EEPROM checking
failure
EEPROM damaged Ask for technical support
Err24 Water shortage
fault
Water shortage of water source Stop the controller Repair
broken wiring or replace
water level switch
Verify if the setting of FD.12
“Water shortage detection
current ratio” is too high, while
FD.10 “Water shortage detection
time” is non-zero and the current
sensing is enabled.
Reduce setting value of
FD.12
Err26 Running time
reached
Accumulated running time
reached set value
Restore factory settings
Err29 Powering time
reached
Accumulated powering time
reached set value
Restore factory settings
Err31 PID feedback loss
when running
Abnormal PID feedback signal Check PID signal
PID feedback signal is below
detect value
Adjust PID feedback detect
value and detect time
Err40 Overtime fault of
fast-current limit
Load too heavy or motor stuck Reduce loador check the
motor
Rate of controller too small Change upper rate controller
Err98
/99
Internal
Communication
Poor contact between keyboard
and control board
Check connect cable
Fault
code
Fault description Possible causes Remedy
fault Keypad failure Look for technical support
Lou Alarm for low
water level at intake
The inlet low-water float ball
terminal is closed for conduction
Check the intake pond for
water shortages
FUL
L
Alarm of high water
level at outlet
The high water level float
terminal of the outlet tank is
closed for conducting
Check to see if the water
level is fu

 