Biến tần HpMont HD09-2s0p7GMS mất 1 pha ra-tmnsoft (1)

Mã lỗi biến tần HpMont HD09-2s0p7GMS

Menu

Mã lỗi biến tần HpMont HD09-2s0p7GMS

Fault Fault reasons Counter-measures
-Lu- DC bus undervoltage At the begining of powering on
and at the end of powering off
Input voltage is too low
Improper wiring leads to
undervoltage of hardware
It is normal status of powering on and
powering off
Please check input power voltage
Please check wiring and wire the
inverter properly
E0001 Inverter acceleration
overcurrent
Improper connection between
inverter and motor
Improper motor parameters
The rating of the used inverter is
too small
Acceleration / deceleration time is
too short
Connect the inverter and motor
properly
Please set correct motor parameters
(F08.00 – F08.03)
Select inverter with higher rating
Please set proper acceleration time
and deceleration time (F03.01, F03.02)
E0002 Inverter deceleration
overcurrent
E0003 Inverter constant
speed overcurrent
E0004 DC bus acceleration
over voltage
Input voltage is too high
Deceleartion time is too short
Improper wiring leads to
overvoltage of hardware
Improper selection of the braking
devices
Please check power input
Please set a proper value for
deceleration time (F03.02)
Please check wiring and wire the
inverter properly
Select according to the recommended
braking devices of section 5.2 Braking
Resistor, page 20
E0005 DC bus deceleration
over voltage
E0006 DC bus constant
speed over voltag
Fault Fault reasons Counter-measures
E0007 Stall overvoltage Bus voltage is too high
The setting of stall overvoltage is
too low
Please check power input or the
function of brake
Set the value of stall overvoltage
properly (F19.19)
E0008 Fault of power
module
Short circuit between phases
output
Short circuit to the ground
Output current is too high
Power module is damaged
Please check the connection and
connect the wire properly
Please check the connection and
connect the wire properly
Please check the connection and
mechanism
Please contact the supplier for
repairing
E0009 Heatsink overheat Ambient temperature is too high
Inverter external ventilation is not
good
Fan fault
Fault occurs to temperature
detection circuit
Please use inverter with higher power
capacity
Improve the ventilation around the
inverter
Replace the cooling fan
Please seek technical support
E0011 CPU fault CPU abnormal Please detect at power on after
completely power outage
Please seek technical support
E0012 Parameters auto
tuning fault
Parameter auto-tuning is time out Please check the motor’s connection
Input the correct motor parameters
(F08.01 – F08.03)
Please seek technical support
E0013 Contactor is not
actuated
Contactor fault
Fault of control circuit
Replace the contactor
Please seek technical support
E0014 Fault of current
detection circuit
Current detection circuit is
damaged
Please contact the supplier for
repairing
E0016 Fault of output phase Output phase disconnectionor
loss
Heavy imbalance of inverter’s
three-phase load
Please check the connection between
inverter and motor
Please check the quality of motor
E0017 Inverter overload Acceleration time is too short
Improper setting of V/f curve or
torque boost leads to over current
Mains supply voltage is too low
Motor load is too high
Adjust acceleration time (F03.01)
Adjust V/f curve (F09.01 – F09.06) or
torque boost (F09.07, F09.08)
Please check mains supply voltage
Please use inverter with proper power
rating
Fault Fault reasons Counter-measures
E0019 Motor overload Improper setting of V/f curve
Mains supply voltage is too low
Normal motor runs for a long time
with heavy load at low speed
Motor runs with blocked torque or
load is too heavy
Adjust thesetting of V/f curve (F09.01 –
F09.06)
Check the power input
Please use special motor
Please check the load and mechanical
transmission devices
E0021 Access fault of
Control board
EEPROM
Memory circuit fault of control
board EEPROM
Please contact the supplier for
repairing
E0024 Fault of external
equipment
Fault terminal of external
equipment operates
Please check external equipment
E0028 SCI communication
time-out
Connection fault of
communication cable
Disconnected or not well
connected
Please check the connection
E0029 SCI communication
error
Connection fault of
communication cable
Disconnected or not well
connected
Communication setting error
Communication data error
Please check the connection
Please check the connection
Please correctly set the
communication format (F17.00), and
the baud rate (F17.01)

 